变频器控制器(ATV-IMC:集成式机器控制器, Integrated Machine Controller) 集成有控制系统功能,用于调整变频器使之适用于特定的应用场合。
施耐德电气及其合作伙伴销售各种预定义的可配置应用程序。SoMachine 是一种专业、高效且开放的OEM 软件解决方案,在单一环境中对整个机械进行开发、配置和调试( 包括逻辑、电机控制、人机界面HMI 以及相关的网络自动化功能)。
SoMachine 让您可以对施耐德电气灵活机器控制(Flexible Machine Control) 中所
有要素进行编程和调试,而灵活机器控制则用于帮助您针对每一机械的要求实现优化的控制解决方案。
在ATV 61 或ATV 71 变频器内只能安装一块ATV-IMC 可编程卡。它可以与另一选件卡( 输入/ 输出扩展卡或通讯卡) 组合使用。ATV-IMC 选件卡不能与ATV-IMC 选件卡组合使用。
ATV-IMC 可编程卡具有:
·10 个逻辑输入
·2 个模拟输入
·6 个逻辑输出
·2 个模拟输出
·一个用于 CANopen® 总线的主站端口
·一个供SoMachine 软件编程使用的mini-USB B 端口。
·一个供SoMachine 软件编程或Modbus TCP 通讯使用的以太网端口。
electrical isolation
Away. And the redundant operation is realized by two redundant field controllers.
Fi8i0f card is a triple can bus protocol interface card (rate 1mbd) used to connect industrial ial “conventional process control station
The i/0 protection unit of the PS is used to receive process signals from the rack mounted i/0 modules supported by the PS. Each field controller PS can only be configured
-Block fi810f card. — The two fi810f interface cards on the redundant PS. can be switched redundantly.

S800 and S900 are distributed i/0 for process control stations. They communicate with their controllers through Prof ibusdp Fieldbus
Communication, which can be installed in the controland PA three levels, DP communication rate can be as high as 12Mb. The CAN (DIN/IS011898 standard) bus
The biggest feature is its super sturdiness and data security. The system of course also supports Modbus. The communication with the intelligent field instrument is through
IART protocol or field bus (31. 25Kb ProfibusPA and FF bus).
The system communication between the operation management level and the process control level is realized by Di giNetS network (Industrial Ethernet/IEEE802.3 standard),
Users can choose the communication transmission medium (ordinary cable or optical fiber) and network topology according to the actual situation of the application.
The popular PC and MS_ Windows 2000 have been widely used in various fields all over the world, becoming the de facto standard computer platform.
tower. The operating station 0S, the engineering station ES and the data gateway GS of the Industrial” system use this platform to ensure the system’s
Versatility, openness and ease of use, and bring great convenience to future technical upgrades and maintenance.
System engineering is very convenient. The configuration language is based on the IE061131 3 industry standard, providing function block diagram (FBD), ladder diagram
(LD), instruction list (IL), sequential function chart (SFC), structured text (ST) and other graphical configuration methods. The system contains about 220 functions
Algorithm library for energy blocks and a basic library with more than 200 graphic symbols and an extended library with a large number of 3D symbols.
The system uses the same set of configuration tool software to complete the configuration and debugging of process level, operation level and even fieldbus instruments, and uses the same

a global database.
The scale of the system is highly scalable, and a single-system supports 1 to a maximum of 100 control stations and 100 operating stations. each control
The station can support several thousand I/0 points at most, and the scale of the whole system can be expanded. The hardware of the system control station is encapsulated in an all-metal shell, which can withstand the most
Harsh industrial environment. The device can be installed either in a cabinet or on a wall. System complies with all current EMC standards and is CE marked
Chi.
Industrial” DCS system design purpose: the most economical engineering investment, the most powerful control function.
Five features of Industria1″ DCS system:
1. All-round integrated control system, integrating DCS & PLC & Field Bus;
2. Using RISC SuperScalar high-speed CPU, with super performance;
Three high reliability, strict industrial application practice, more than 1000 sets of application performance in China;
4. It has good openness, flexibility and scalability;
Fifth, the project is easy, the interface is friendly, and the maintenance is simple;
2. Industria1″ system communication
Industrial” system uses 