Profibus-DP被设计用来在中心控制器模块(比如PLC或PC)之间迅速地传送过程数据,并在现场级别中分散现场模块(此如I/O模块、驱动和真空管)。通信主要以循环方式进行。对于智能现场模块,在循环地传送数据过程中的参数分配、诊断及告警处理还需要非循环的通信功能。
利用Profibus-DP可实现单一主设备系统和多个主设备系统。多个主设备系统由功能独立的子系统构成,每个子系统包括一个主设备和一部分从设备,所有这些集成在一个完整的系统中。
The field controller supports various field buses such as PROFIBUS, which is the most widely used open field bus in the world
Line international standard, divided into FMS, DP and PA, DP communication rate can be as high as 12MB. Can (din/is011898 standard) bus
The biggest feature is its super robustness and data security. The system also supports MODBUS. The communication with intelligent field instruments is through

IART protocol or fieldbus (31.25kb profibuspa and FF Bus).
The system communication between the operation management level and the process control level is realized by the di ginets network (Industrial Ethernet /iee802.3 standard),
The user can select the communication transmission medium (ordinary cable or optical fiber) and network topology structure according to the actual situation of the application.
Popular PC and MS_ Wi ndows2000 has been widely used in various fields all over the world and has become the de facto standard computer platform
Set. The operating station 0s, engineer station es and data gateway GS of the industrial “system have adopted this platform, thus ensuring the
It is universal, open and easy to use, and brings great convenience for future technology upgrading and maintenance.
System engineering configuration is very convenient. The configuration language is based on ie0611313 industrial standard and provides function block diagram (FBD) and ladder diagram
(LD), instruction list (IL), sequential function diagram (SFC), structured text (st) and other graphical configuration modes. The system contains about 220 functions
The algorithm library of energy block, the basic library with more than 200 graphic symbols and the extended library with a large number of 3D symbols.

The system uses the same set of configuration tool software to complete the configuration and commissioning of process level, operation level and even fieldbus instruments, and uses the same
A global database.
The system scale has strong scalability. The single system supports 1 to 100 control stations and 100 operation stations at most. Each control

The station can